Fine-Tuning Open Loop Vector Control For Pm Motors - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

4.8 Fine Tuning during Test Runs (Adjust the Control Function)

Fine-Tuning Open Loop Vector Control for PM Motors

Issue
Unsatisfactory motor performance
Unsatisfactory motor torque and
speed response
• Oscillation at start.
• Motor stalls.
There is too much current during
deceleration.
Stalling or oscillation occurs when
load is applied during constant speed
Hunting or oscillation
The drive detects STPo [Motor Step-
Out Detected] fault when the load is
not too high.
The drive detected stalling or STPo
[Motor Step-Out Detected] at high
speed and maximum output voltage.
*1
Default value changes when E5-01 [PM Mot Code Selection] and o2-04 [Drive KVA Selection] values change.
158
Table 4.21 Parameters for Fine-Tuning Performance in OLV/PM
Parameter Number
• Check the settings for E1-06 [Base Frequency], E1-
04 [Max Output Frequency].
• Check the E5: PM MOTOR SETTINGS parameters
E1: V/F PARAMETER
and make sure that all motor data has been set
MOTOR 1 parameters,
correctly.
E5: PM MOTOR SETTINGS
Note:
parameters
Do not set E5-05 [PM Mot Resistance (Ohms/
Phase)] to a line-to-line resistance value.
• Do Auto-Tuning.
Adjust to match the load inertia ratio of the motor and
n8-55 [Load Inertia]
machine.
n8-45 [SpdFbck Det.Gain]
Decrease the setting value in increments of 0.05.
Adjust the setting value.
Note:
C4-01 [Trq Comp Gain]
Setting this value too high can cause
overcompensation and motor oscillation.
n8-51 [Ac/Dec Pull-In
Increase the setting value in increments of 5%.
Current]
Use DC Injection Braking at start.
• b2-02 [DCI Braking
Note:
Current]
This can cause the motor to rotate in reverse for
• b2-03 [DCInj Time@Start]
approximately 1/8 of a turn at start.
Increase the setting value.
Note:
n8-55 [Load Inertia]
When operating a single motor or with a minimum
amount of inertia, setting this value too high can
cause motor oscillation.
n8-79 [Pull-In
Set n8-79 < n8-51.
Curr@Deceleration]
n8-47 [Pull-In Comp.Time
Decrease the setting value in increments of 0.2 s.
Constant]
n8-48 [Pull-In Current (for
Increase the setting value in increments of 5%.
PM Motors)]
Increase the setting value.
Note:
n8-55 [Load Inertia]
When operating a single motor or with a minimum
amount of inertia, setting this value too high can
cause motor oscillation.
n8-45 [SpdFbck Det.Gain]
Increase the setting value in increments of 0.05.
• E5-09 [PM BackEMF
• Adjust the setting value.
Vpeak (mV/(rad/ s))]
• Examine the motor code on the motor nameplate or
• E5-24 [PM BackEMF L-L
the data sheet, then set correct values for E5-09 or
E5-24.
Vrms (mV/rpm)]
n8-62 [Output Volt Limit
Set to a value lower than the actual input voltage.
Level]
Solution
1
0.80
0.00
50%
• b2-02: 50%
• b2-03: 0.0 s
1
0%
5.0 s
30%
1
0.80
*1
• 400.0 V
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
Recommended Setting
Setting
-
-
Near the actual load inertia
ratio.
-
1.00
-
• b2-02: Adjust as necessary.
• b2-03: 0.5 s
Near to the actual load inertia
ratio.
Note:
When n8-
79 = 0, the
drive will
apply the
Decrease in increments of 5%.
n8-51
setting to
the pull-in
current
during
decelera
tion.
-
-
Near to the actual load inertia
ratio.
-
• Yaskawa motor
Set the motor code from
the motor nameplate.
• Motor from another
manufacturer
Set the values from the test
report.
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents