12.3 C: TUNING
1 : 0.1s
Sets acceleration and deceleration times in 0.1 s units. The setting range is 0.0 to 6000.0 s.
C1-11 Ac/Dec Switch Frequency
No.
Name
(Hex.)
C1-11
Ac/Dec Switch Frequency
(020A)
When output frequency get C1-11 value, the drive automatically switches the acceleration and deceleration times.
Set this parameter to 0.0 to disable this function.
Table 12.17
lists the possible combinations of acceleration and deceleration time switchover frequencies and the
acceleration times for the Motor 2 Selection function.
Table 12.17 Motor and Acceleration and Deceleration Time Combination
C1-11
Less than the setting value
Equal to or more than the setting
value
C1-14 Ac/Dec Base Frequency
No.
Name
(Hex.)
C1-14
Ac/Dec Base Frequency
(0264)
The acceleration and deceleration rates set in C1-01 to C1-09 [Accel Time 1 to Decel Time 4, Fast Stop Time] will
change when the value of C1-14 changes.
• When C1-14 = 0.0 Hz
– C1-01, C1-03, C1-05, C1-07 [Accel Time 1 to Accel Time 4]: Time to accelerate from 0 Hz to E1-04 [Max
Output Frequency]
– C1-02, C1-04, C1-06, C1-08 [Decel Time 1 to Decel Time 4], C1-09 [Fast Stop Time]: Time to decelerate
from E1-04 to 0 Hz.
Figure 12.41 Example 1: Acceleration/Deceleration Rate (When C1-14 = 0 Hz, E1-04 = 60 Hz, and the Frequency
• When C1-14 ≠ 0.0 Hz
568
V/f
CL-V/f
OLV
CLV
Sets the frequency at which the drive will automatically change acceleration and deceleration
times.
Figure 12.40 Accel/Decel Time Switching Frequency
Motor 1
Acceleration Time
Deceleration Time
C1-07 [Accel Time 4]
C1-08 [Decel Time 4]
C1-01 [Accel Time 1]
C1-02 [Decel Time 1]
V/f
CL-V/f
OLV
CLV
Sets the base frequency used to calculate acceleration and deceleration rates.
Reference is 60 Hz)
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Acceleration Time
C1-07 [Accel Time 4]
C1-05 [Accel Time 3]
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
Determined by A1-02
(0.0 - 590.0 Hz)
Motor 2
Deceleration Time
C1-08 [Decel Time 4]
C1-06 [Decel Time 3]
Default
(Range)
0.0 Hz
(0.0 - 590.0 Hz)