3.8 External Interlock

3.8

External Interlock

For applications that will have unwanted effects on the system if the drive stops, make an interlock between fault
relay output (1NO, 1NC, 1CM) and the MFDO Drive Ready signal.
Drive Ready
When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which Drive Ready
[H2-xx = 1] is set will enter the ON status.
In these conditions, Drive Ready is OFF and the drive ignores Run commands:
• The drive is de-energized
• During a fault
• There is problem with the control power supply
• There is a parameter setting error that will not let the drive run, although a Run command is entered
• An overvoltage or undervoltage fault occurs when the Run command is entered
• The drive is in Programming Mode.
Interlock Circuit Example
This is an example of how two drives that run one application use the Drive Ready and Fault output signals to
interlock with the controller.
Terminal
Output Signal
Parameter Settings for Output Signal
1NO, 1NC, 1CM
Fault
-
2NO, 2CM
Drive Ready
H2-01 = 1 [Drive Ready]
Figure 3.50 Interlock Circuit Example