Omron Q2A Series Technical Manual page 425

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

No.
Name
(Hex.)
F6-25
MLII Watchdog Error
Sel
(03C9)
F6-26
MLII bUS Err Detected
(03CA)
F6-30
PROFI-DP Address
(03CB)
F6-31
PROFI-DP Clear
Command Mode
(03CC)
F6-32
PROFI-DP Data Format
Select
(03CD)
F6-35
CANopen Address
(03D0)
F6-36
CANopen BaudRate
(03D1)
F6-45
BACnet Address
(02FB)
F6-46
BACnet BaudRate
(02FC)
F6-47
BACNet Rx-Tx Wait
Time
(02FD)
F6-48
BACnet DevOb Id0
(02FE)
F6-49
BACnet DevOb Id1
(02FF)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects an E5 [MECHATROLINK Watchdog Timer Err].
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times that the option must detect a bUS alarm to cause a bUS
[Option Communication Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for PROFIBUS-DP communication. Restart the drive after
changing this setting.
Note:
Be sure to set a node address that is different than all other node addresses.
V/f
CL-V/f
OLV
CLV
AOLV
Sets what the drive will do after it receives the Clear Mode command.
0 : Reset
1 : Hold Previous State
V/f
CL-V/f
OLV
CLV
AOLV
Sets the data format of PROFIBUS-DP communication. Restart the drive after changing
this setting.
0 : PPO Type
1 : Conventional
2 : PPO (bit0)
3 : PPO (Enter)
4 : Conv (Enter)
5 : PPO (bit0,Enter)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for CANopen communication. Restart the drive after changing
this setting.
Note:
Be sure to set an address that is different than all other node addresses. Do not set
this parameter to 0. Incorrect parameter settings will cause AEr [Station Address
Setting Error] errors and the L.ERR LED on the option will come on.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the CANopen communications speed. Restart the drive after you change this
setting.
0 : Auto-Detection
1 : 10 kbps
2 : 20 kbps
3 : 50 kbps
4 : 125 kbps
5 : 250 kbps
6 : 500 kbps
7 : 800 kbps
8 : 1 Mbps
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node address for BACnet communication.
Note:
Set a node address that is unique. Do not set this parameter to a value of 0.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the BACnet communications speed.
1 : 1200 bps
2 : 2400 bps
3 : 4800 bps
4 : 9600 bps
5 : 19.2 kbps
6 : 38.4 kbps
7 : 57.6 kbps
8 : 76.8 kbps
9 : 115.2 kbps
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wait time for the drive to receive and send BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of BACnet communication addresses.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of BACnet communication addresses.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: OPTIONS
Default
Ref.
(Range)
1
653
(0 - 3)
2 times
654
(2 - 10 times)
0
654
(0 - 125)
0
654
(0, 1)
0
654
(0 - 5)
0
655
(0 - 126)
0
655
(0 - 8)
1
655
(0 - 127)
3
655
(0 - 8)
5 ms
656
(5 - 65 ms)
0
656
(0 - FFFF)
0
656
(0 - 3F)
425
11