H4: Analog Outputs - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Setting
Function
D
GenerTrqLim
E
OvUntrq Level
F
PID Fbk
10
PID SetPoint
11
Diff PIDFbk
12
AcDcTimeGain
13
DCInjBrakCurr
14
StallPLev@Rn
15
OutFLowLimSel
16
Mot PTC Input
30
Q2pack AI1
31
Q2pack AI1
32
Q2pack AI3

H4: ANALOG OUTPUTS

No.
Name
(Hex.)
H4-01
AO1 An.Out Select
(041D)
H4-02
AO1 An.Out Gain
(041E)
RUN
H4-03
AO1 An.Out Bias
(041F)
RUN
H4-04
AO2 An.Out Select
(0420)
H4-05
AO2 An.Out Gain
(0421)
RUN
H4-06
AO2 An.Out Bias
(0422)
RUN
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the
motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the overtorque/undertorque detection level.
Note:
Use this function with L6-01 [Trq Det1 Select]. This parameter functions as an alternative to L6-02 [Trq Det1
Level].
V/f
CL-V/f
OLV
CLV
AOLV
Enters the PID feedback value.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the PID setpoint.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the gain used for C1-01 to C1-08 [Accel Time 1 to Decel Time 4] if the full scale analog
signal (10 V or 20 mA) is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the current level used for DC Injection Braking if the drive rated output current is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the output frequency lower limit level if E1-04 [Max Output Frequency] = 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor if the
current value when the 10 V (or 20 mA) analog signal is input is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number to send from MFAO terminal AO1.
Set the x-xx part of the U: MONITORS. For example, set H4-01 = 102 to monitor U1-02
[Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AO1.
Sets the analog signal output level from the terminal AO1 at 10 V or 20 mA as 100%
when an output for monitoring items is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AO1.
Set the level of the analog signal sent from terminal AO1 at 10 V or 20 mA as 100%
when an output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from the MFAO terminal AO2.
Set the x-xx part of the U: MONITORS. For example, set H4-04 to 102 to monitor U1-
02 [Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AO2.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AO2 terminal at 10 V or 20 mA as 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AO2.
Set the level of the analog signal sent from the AO2 terminal at 10 V or 20 mA as 100%
when an output for monitoring items is 0%.
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: TERMINALS
Ref.
720
720
721
721
721
721
721
722
722
722
722
722
723
Default
Ref.
(Range)
102
724
(000 - 999)
100.0%
724
(-999.9 - +999.9%)
0.0%
725
(-999.9 - +999.9%)
103
725
(000 - 999)
50.0%
725
(-999.9 - +999.9%)
0.0%
725
(-999.9 - +999.9%)
443
11

Hide quick links:

Advertisement

Table of Contents
loading