11.3 b: APPLICATION

b6: DWELL FUNCTION

No.
Name
(Hex.)
b6-01
Dwell Ref.@Start
(01B6)
b6-02
Dwell Time@Start
(01B7)
b6-03
Dwell Ref@Stop
(01B8)
b6-04
Dwell Time@Stop
(01B9)

b7: DROOP CONTROL

No.
Name
(Hex.)
b7-01
Droop Ctrl Gain
(01CA)
RUN
b7-02
Droop Ctrl Delay Time
(01CB)
RUN
b7-03
Droop Ctrl Limit
Selection
(017E)

b8: ENERGY SAVING

No.
Name
(Hex.)
b8-01
eSave Ctrl Selection
(01CC)
b8-02
eSave Ctrl Gain
(01CD)
RUN
Expert
b8-03
eSave Filter Time
(01CE)
RUN
Expert
b8-04
eSave Coef. Value
(01CF)
Expert
b8-05
Power Det.Filter Time
(01D0)
Expert
b8-06
Srch Op.Volt Limit
(01D1)
Expert
b8-16
PM eSave Coef.Ki
(01F8)
Expert
b8-17
PM eSave Coef.Kt
(01F9)
Expert
404
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output frequency that the drive will hold momentarily when the motor starts.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the drive will hold the output frequency when the motor
starts.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time for the drive to hold the output frequency when ramping to stop
the motor.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount of deceleration when the torque reference is at 100% of Maximum
Output Frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of Droop control. Decrease this setting when drive response is
slow. Increase this setting when hunting or oscillation occur.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Droop control limit function.
0 : Disabled
1 : Enabled
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
2 : Search Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The
default setting is for Yaskawa motors.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to measure output power.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the voltage limit for Search Operation as a percentage where motor rated voltage is
a setting value of 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets torque linearity. This parameter uses the Ki value from the motor nameplate.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets torque linearity. This parameter uses the Kt value from the motor nameplate.
Usually it is not necessary to change this setting.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
Ref.
(Range)
0.0
556
(Determined by A1-02)
0.0 s
556
(0.0 - 10.0 s)
0.0
556
(Determined by A1-02)
0.0 s
556
(0.0 - 10.0 s)
Default
Ref.
(Range)
0.0%
557
(0.0 - 100.0%)
0.05 s
557
(0.03 - 2.00 s)
1
557
(0, 1)
Default
Ref.
(Range)
0
558
(Determined by A1-02)
Determined by A1-02
558
(0.0 - 10.0)
Determined by A1-02,
558
C6-01, and o2-04
(0.00 - 10.00 s)
Determined by C6-01,
558
E2-11, o2-04
(0.00 - 655.00)
20 ms
558
(0 - 2000 ms)
0%
559
(0 - 100%)
1.00
559
(0.00 - 3.00)
1.00
559
(0.00 - 3.00)

Hide quick links:

Advertisement

Table of Contents
loading