Terminal
Name (Default)
MFDI selection 1
DI1
(ON: Forward run OFF: Stop)
MFDI selection 2
DI2
(ON: Reverse run OFF: Stop)
MFDI selection 3
DI3
(External fault (N.O.))
MFDI selection 4
DI4
(Fault reset)
MFDI selection 5
DI5
(Multi-step speed reference 1)
MFDI selection 6
DI6
(Multi-step speed reference 2)
MFDI selection 7
DI7
(Jog command)
MFDI selection 8
DI8
(Baseblock command (N.O.))
D0V
MFDI power supply 0 V
DIC
MFDI selection common
D24V
MFDI power supply +24 Vdc
Terminal
Name (Default)
H1
Safe Disable input 1
H2
Safe Disable input 2
HC
Safe Disable function common
Terminal
Name (Default)
Master frequency reference pulse train input
PI
(Master frequency reference)
+10V
Power supply for frequency setting
-10V
Power supply for frequency setting
MFAI1
AI1
(Master frequency reference)
MFAI2
AI2
(Combined to terminal A1)
MFAI3/PTC input
AI3
(Auxiliary frequency reference)
A0V
Frequency reference common
GND
Connecting shielded cable
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Table 3.4 Digital Inputs
• Photocoupler
• 24 V, 6 mA
Note:
Install the wire jumpers between terminals DIC-D24V and DIC-D0V to set the MFDI power supply (sinking/
sourcing mode or internal/external power supply).
• Sinking Mode: Install a jumper between terminals DIC and D24V.
NOTICE: Do not close the circuit between terminals DIC and D0V in Sinking
Mode. Failure to obey will cause damage to the drive.
• Sourcing Mode: Install a jumper between terminals DIC and D0V.
NOTICE: Do not close the circuit between terminals DIC and D24V in Source
Mode. Failure to obey will cause damage to the drive.
• External power supply: No jumper necessary between terminals DIC-D0V and terminals DIC-D24V.
MFDI power supply, 24 V (maximum 150 mA)
NOTICE: Do not close the circuit between terminals D24V and D0V. Failure to
obey will cause damage to the drive.
Table 3.5 Safe Disable Input
Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.
• 24 V, 6 mA
• ON: Normal operation
• OFF: Coasting motor
• Internal impedance 4.7 kΩ
• OFF Minimum OFF time of 2 ms.
Safe Disable function common
NOTICE: Do not close the circuit between terminals HC and D0V. Failure to obey
will cause damage to the drive.
Table 3.6 Master Frequency Reference
• Response frequency: 0 Hz to 32 kHz
• H level duty: 30% to 70%
• H level voltage: 3.5 V to 13.2 V
• L level voltage: 0.0 V to 0.8 V
• Input impedance: 3 kΩ
10.5 V (allowable current 20 mA maximum)
-10.5 V (allowable current 20 mA maximum)
Voltage input or current input
Select terminal AI1 with DIP switch S1-1 and H3-01 [AI1 Signal Level Select].
Select terminal AI2 with DIP switch S1-2 and H3-09 [AI2 Signal Level Select].
• -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
• 0 V to 10 V/100% (input impedance: 20 kΩ)
• 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
• Voltage input or current input
Select with DIP switch S1-3 and H3-05 [AI3 Signal Level Select].
– -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)
– 0 V to 10 V/100% (input impedance: 20 kΩ)
– 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)
• PTC input (Motor Overheat Protection)
Set DIP switch S4 to "PTC" and set DIP switch S1-3 to "V" to set terminal AI3 for PTC input.
0 V
3.5 Control Circuit Wiring
Function (Signal Level)
Function (Signal Level)
Function (Signal Level)
-
3
87