Omron Q2A Series Technical Manual page 765

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

• When you manually clear a fault after the drive triggers protective functions.
• When you re-energize the drive.
L5-02 Fault@Reset Select
No.
Name
(Hex.)
L5-02
Fault@Reset Select
(049F)
1 : Disable Fault Output
2 : Enable Fault Output
L5-04 Interval Reset Time
No.
Name
(Hex.)
L5-04
Interval Reset Time
(046C)
L5-05 Reset Method
No.
Name
(Hex.)
L5-05
Reset Method
(0467)
1 : Continuous
Counts the number of successful fault resets through Auto Restart.
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
2 : Use L5-04 Time
Counts the number of successful and unsuccessful fault resets through Auto Restart. The drive does the Auto
Restart process again in the intervals set in L5-04 [Interval Reset Time].
When this value > L5-01, the drive will send a fault signal and fault code to the keypad and the motor will coast to
stop.
L5-07 OL1-4 Auto-Reset Select
No.
Name
(Hex.)
L5-07
OL1-4 Auto-Reset Select
(0B2A)
0 : Disabled
1 : Enabled(—/—/—/oL4)
L5-08 U/OV,OH,GF A-Reset Select
No.
Name
(Hex.)
L5-08
U/OV,OH,GF A-Reset
Select
(0B2B)
0 : Disabled
1 : Enabled(—/–/—/GF)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = 3] while the
drive is automatically restarting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time interval between each Auto Restart attempt. Set L5-05 = 1 [Reset Method =
Continuous] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the count method for the Auto Restart operation.
V/f
CL-V/f
OLV
CLV
AOLV
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set
oL1, oL2, oL3, and oL4, in order.
Figure 12.134 Setting Digits and Fault Code
V/f
CL-V/f
OLV
CLV
AOLV
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to right,
the digits set Uv1, ov, oH1, and GF, in order.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 L: PROTECTION
Default
(Range)
1
(1, 2)
Default
(Range)
10.0 s
(0.5 - 600.0 s)
Default
(Range)
1
(1, 2)
Default
(Range)
1111
(0000 - 1111)
Default
(Range)
1111
(0000 - 1111)
765
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents