4.8 Fine Tuning during Test Runs (Adjust the Control Function)
Table 4.18 Parameters for Fine Tuning the Drive (Open Loop Vector Control Method)
Issue
• Torque or speed response are
slow.
• Hunting or oscillation at mid-
range speeds (10 Hz to 40 Hz)
ov [overvoltage] occurs when the
drive stops accelerating, starts to
decelerate, or when there are large
changes in the load.
• Torque or speed response are
slow.
• Hunting or oscillation
• Speed response is slow.
• Speed is not stable.
Speed precision is unsatisfactory.
• The volume of the motor
excitation sound is too high.
• Hunting or oscillation at low
speeds (10 Hz or lower)
• Torque at low speeds (10 Hz or
lower) is not sufficient. speed
response is slow.
• Speed response is slow.
• Large initial vibration at start up.
*1
Default value changes when A1-02 [Control Method] and o2-04 [Drive KVA Selection] values change.
*2
Default value changes when A1-02 [Control Method] and E1-03 [V/f Pattern Selection] values change.
*3
Default value changes when Drive KVA Selection and ND/HD Duty Selection values change.
*4
Recommended settings are for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
156
Parameter Number
• To increase the speed of torque or speed response,
decrease the setting value in increments of 0.05.
n2-01 [AFR Gain]
• If hunting or oscillation occur, decrease the setting
value in increments of 0.05.
• To increase the speed of torque or speed response,
decrease the setting value in increments of 10 ms
and examine the response.
• If hunting or oscillation occur or if the load inertia is
too much, increase the setting value in increments of
50 ms and examine the response.
n2-02 [AFR Time 1]
Note:
Make sure that this parameter setting is: n2-02 ≤
n2-03 [AFR Time 2] holds true.
When you adjust n2-02, you must also increase
theC4-02 [Trq Comp Delay Time] value by the
same ratio.
• If ov occurs, increase the setting value in increments
of 50 ms and examine the response.
• If the response is not sufficient, decrease the setting
value in increments of 10 ms and examine the
response.
n2-03 [AFR Time 2]
Note:
Make sure that this parameter setting is: n2-02
[AFR Time 1] ≤ n2-03. When you adjust n2-03 you
must also increase the C4-06 [M2 Trq Comp Delay
Time] value by the same ratio.
• If ov occurs, increase the setting value in increments
of 10 ms and examine the response.
• If the response is not sufficient, decrease the setting
value in increments of 2 ms and examine the
response.
C4-06 [M2 Trq Comp Delay
Time]
Note:
Make sure that this parameter setting is: C4-02 [Trq
Comp Delay Time] ≤ C4-06.
When you adjust C4-06, you must also increase the
n2-03 [AFR Time 2] value by the same ratio.
• If torque or speed response are slow, decrease the
setting value in increments of 2 ms.
• If hunting or oscillation occur, increase the setting
value in increments of 10 ms.
C4-02 [Trq Comp Delay
Note:
Time]
Make sure that this parameter setting is: C4-02 ≤
C4-06 M2 Trq Comp Delay Time.
When you adjust C4-02, you must also increase the
n2-02 AFR Time 1 value by the same ratio.
• If speed response is slow, decrease the setting value
in increments of 10 ms.
C3-02 [Slip Comp Delay
Time]
• If speed is not stable, increase the value in
increments of 10 ms.
• If speed is too slow, increase the setting value in
increments of 0.1.
C3-01 [Slip Comp Gain]
• If speed is too fast, decrease the setting value in
increments of 0.1.
• If the volume of the motor excitation sound is too
high, increase the carrier frequency.
C6-02 [Carrier Frequency
Selection]
• If hunting or oscillation occur at low speeds,
decrease the carrier frequency.
• If torque or speed response are slow, increase the
setting value.
• E1-08 [Mid A Voltage]
• If there is large initial vibration at start up, decrease
the setting value
• E1-10 [Min Output
Voltage]
Note:
If the setting value is set too high, a large torque
reference may be output even with light loads.
Solution
1.00
50 ms
750 ms
150 ms
20 ms
200 ms
1.0
1 (2 kHz)
• E1-08: 11.0
• E1-10: 2.0
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
Recommended Setting
Setting
0.50 - 2.00
50 - 2000 ms
750 - 2000 ms
150 - 750 ms
*1
*1
20 - 100 ms
*1
100 - 500 ms
*2
0.5 - 1.5
*3
0 to upper limit value
*2
Default setting +/- 2 V
*2
*4