Omron Q2A Series Technical Manual page 552

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.2 b: APPLICATION
Note:
• This parameter is disabled when set to 0.0 Hz.
• When the integrator ramp limit is enabled (b5-53 > 0.0 Hz), the PID integrator value limit is the range set by the output frequency ±b5-
53.
• When the PID feedback changes quickly, gradually decrease the value of this parameter in increments of 0.1 Hz to decrease the speed
of the response of PID control.
b5-54 PID Softstarter Selection
No.
Name
(Hex.)
b5-54
PID Softstarter Selection
(0BB7)
Table 12.13
shows how the soft-starter responds to PID input/output.
Selection
Soft Starter 1
Soft Starter 2
0 : Disab PID Softstart
The soft starter process occurs downstream from the PID function. The PID function input functions as the
frequency reference, the PID function output functions as the soft starter input, and the soft starter output
functions as the output frequency.
1 : Enab PID Softstart
The soft starter process occurs upstream from the PID function. The soft starter input functions as the frequency
reference, the soft starter output functions as the soft starter input, and the PID function output functions as the
output frequency.
b5-55 PID Fback Mon Selection
No.
Name
(Hex.)
b5-55
PID Fback Mon Selection
(0BE1)
Note:
• You cannot select parameter U5-xx.
• This parameter is disabled when set to 000.
b5-56 PID FdbkMon Gain
No.
Name
(Hex.)
b5-56
PID FdbkMon Gain
(0BE2)
Note:
Set b5-18 = 1 [b5-19 PID SP Selection = Enabled] to enable this parameter.
b5-57 PID FdbkMon Bias
No.
Name
(Hex.)
b5-57
PID FdbkMon Bias
(11DD)
b5-58 to b5-60 PID Setpoint 2 to PID Setpoint 4
No.
Name
(Hex.)
b5-58 to b5-60
PID Setpoint 2 to PID
Setpoint 4
(1182 - 1184)
RUN
552
V/f
CL-V/f
OLV
Sets how the soft-starter responds to PID input/output.
Table 12.13 Soft Starter and PID Input/Output
PID Frequency Reference
PID Frequency Reference
Input
Frequency Reference
Soft Starter Output
V/f
CL-V/f
OLV
Sets the monitor for PID Feedback (Ux-xx).
V/f
CL-V/f
OLV
Sets the gain for the monitor specified in b5-55 [PID Fback Mon Selection].
V/f
CL-V/f
OLV
Sets the bias for the monitor specified in b5-55 [PID Fback Mon Selection].
V/f
CL-V/f
OLV
Sets the PID setpoint when H1-xx = 77 or 78 [MFDI Function Select = PID SP Selection 1/2].
This value is a percentage where E1-04 [Max Output Frequency] setting = a setting value of
100%.
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Soft Starter Input
Output
Soft Starter Input
PID Frequency Reference Output
Output frequency
Frequency Reference
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Soft Starter Output
Output frequency
PID Frequency Reference Input
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
1
(0, 1)
Default
(Range)
000
(000 - 999)
Default
(Range)
1.00
(0.00 - 10.00)
Default
(Range)
0.00
(-10.00 - +10.00)
Default
(Range)
0.00%
(0.00 - 100.00%)