12.8 L: PROTECTION
Overtorque
L6-01 Trq Det1 Select
No.
Name
(Hex.)
L6-01
Trq Det1 Select
(04A1)
The drive detects overtorque if the motor current or output torque is more than the level set in L6-02 [Trq Det1
Level] for the length of time set in L6-03 [Trq Det1 Time]. The drive detects undertorque if the motor current or
output torque is less than the level set in L6-02 for the length the time set in L6-03.
0 : Disabled
1 : Enabled
The behavior is adjusted using parameters L6-50 [Trq Det1 Type], L6-51 [Trq Det1 Action], and L6-52 [Trq Det1
Condition].
L6-02 Trq Det1 Level
No.
Name
(Hex.)
L6-02
Trq Det1 Level
(04A2)
Note:
• Set the torque detection level as a percentage of the drive rated output current in all control methods to set the mechanical weakening
detection level.
• You can also use an analog input terminal to supply the torque detection level. To enable this function, set H3-xx = E [AI Function
Select = OvUntrq Level]. If you set L6-02 and H3-x = E, the analog input is most important and the drive disables L6-02.
L6-03 Trq Det1 Time
No.
Name
(Hex.)
L6-03
Trq Det1 Time
(04A3)
L6-04 Trq Det2 Select
No.
Name
(Hex.)
L6-04
Trq Det2 Select
(04A4)
The drive detects overtorque if the motor current or output torque is more than the level set in L6-05 [Trq Det2
Level] for the length of time set in L6-06 [Trq Det2 Time]. The drive detects undertorque if the motor current or
output torque is less than the level set in L6-05 for the length the time set in L6-06. Adjust the conditions using
parameters L6-53, L6-54, and L6-55 [Trq Det2 Type, Trq Det2 Action, and Trq Det2 Condition].
0 : Disabled
1 : Enabled
L6-05 Trq Det2 Level
No.
Name
(Hex.)
L6-05
Trq Det2 Level
(04A5)
768
Configuration Parameter
Detection Criteria
Detection Level
Detection Time
V/f
CL-V/f
OLV
CLV
Enables overtorque and undertorque detection and the operation of drives (operation status) after
detection.
V/f
CL-V/f
OLV
CLV
Sets the detection level for Overtorque/Undertorque Detection 1. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
Sets the detection time for Overtorque/Undertorque Detection 1.
V/f
CL-V/f
OLV
CLV
Sets the speed range that detects overtorque and undertorque and the operation of drives
(operation status) after detection.
V/f
CL-V/f
OLV
CLV
Sets the detection level for Overtorque/Undertorque Detection 2. In V/f control, drive rated output
current = 100% value. In vector control, motor rated torque = 100% value.
L6-01
L6-02
L6-03
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Mechanical Deterioration Detection
Default
(Range)
0
(0, 1)
Default
(Range)
150%
(0 - 300%)
Default
(Range)
0.1 s
(0.0 - 10.0 s)
Default
(Range)
0
(0 - 8)
Default
(Range)
150%
(0 - 300%)