12.8 L: PROTECTION
L4-06 Freq.Ref@RefLoss
No.
Name
(Hex.)
L4-06
Freq.Ref@RefLoss
(04C2)
Set L4-05 = 2 [FrefLoss Det.Selection = Run@L4-06PrevRef] to enable this parameter.
L4-07 SpAgree Det.Selection
No.
Name
(Hex.)
L4-07
SpAgree Det.Selection
(0470)
1 : No Detect@BB
Detects the frequency while the drive is operating. When the drive turns off its output, it will not detect frequency.
2 : Always Detect

L5: FAULT RESTART

The Auto Restart function tries to keep machines operating when the drive detects a transient fault.
The drive can do a self-diagnostic check and continue the operation after a fault has occurred. If the cause of the
fault goes away, the drive does speed search and restarts. It will not stop and the drive will not record a fault
history. Use L5-02 [Fault@Reset Select] to select the operation of fault relay signals during Auto Restart
operation.
Sets if the drive will do Auto Restart and the number of times the drive will try to do Auto Restart in a set time. If
the number of Auto Restart tries is more than the set value during the set time, drive output shuts off and operation
stops. If this happens, remove the cause of the fault and manually restart the drive.
DANGER! Sudden Movement Hazard. Failure to obey can cause death or serious injury. Do not use the fault restart function in
hoist or lifting applications.
The drive can do Auto Restart when these faults occur:
Note:
You can disable Auto Restart for faults if you must not restart the machine after the fault.
Fault
GF
Ground Fault
LF
Output Phase Loss
oC
Overcurrent
oH1
Heatsink Overheat
oL1
Motor Overload
oL2
Drive Overload
oL3
Overtorque Detection 1
oL4
Overtorque Detection 2
*1
Uv1 is the target for the auto restart process when L2-01 = 1 [RideThru@PwrLoss = Enabled], and L2-50 = 0, 1, 2, 3
[RidThruMode@PwrLoss = Timer Controlled, While CPU Active, KEB Mode, KEB Stop Mode].
L5-01 Auto-Reset Attempts
No.
Name
(Hex.)
L5-01
Auto-Reset Attempts
(049E)
The drive resets the number of Auto Restart attempts to 0 in these conditions:
• The drive operates correctly for 10 minutes after a fault restart.
764
V/f
CL-V/f
OLV
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before the drive
detected the loss.
V/f
CL-V/f
OLV
Sets the condition that activates speed detection.
Table 12.54 List of Faults during which Auto Restart is Available
Parameters to Disable
Name
Auto Restart
L5-08
-
-
L5-08
L5-07
L5-07
L5-07
L5-07
V/f
CL-V/f
OLV
Sets the number of times that the drive will try to restart.
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Fault
ov
PF
rH
rr
STPo
Uv1
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Parameters to Disable
Name
Overvoltage
Input Phase Loss
Braking Resistor Overheat
Dynamic Braking
Transistor Fault
Motor Step-Out Detected
*1
DC Bus Undervoltage
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
80.0%
(0.0 - 100.0%)
Default
(Range)
1
(1, 2)
Auto Restart
L5-08
-
-
-
-
L5-08
Default
(Range)
0
(0 - 10 times)