Omron Q2A Series Technical Manual page 529

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

b2-08 MagFlux Comp Value
No.
Name
(Hex.)
b2-08
MagFlux Comp Value
(0190)
This parameter starts a high-capacity motor (motors with a large secondary circuit time constant). This function
can quickly increase motor flux to make high starting torque (a process called initial excitation).
The DC Injection Braking at start current level changes linearly from the value set in b2-08 to the value set in E2-
03, as shown in
Figure
12.21.
Figure 12.21 DC Current Level during DC Injection Braking at Start
Note:
• If b2-08 < 100%, flux will develop very slowly.
• When b2-08 = 0% the DC current level will be the DC Injection current set in b2-02 [DCI Braking Current].
• If b2-08 is set too high, DC Injection Braking at start will make a loud audible noise. Adjust b2-08 to decrease the volume to the
permitted level.
b2-12 SCB Time@Start
No.
Name
(Hex.)
b2-12
SCB Time@Start
(01BA)
This function restarts a stopped PM motor. The drive short circuits all three motor phases to make braking torque
in the motor.
Set this parameter to 0.00 to disable the function.
Note:
• Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external
forces.
• Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
b2-13 SCB Time@Stop
No.
Name
(Hex.)
b2-13
SCB Time@Stop
(01BB)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Short Circuit Braking operates for the time set in b2-13 when output frequency is less than the value set in b2-01
[ZSpd/DCI Threshold] or E1-09 [Min Output Frequency].
Set this parameter to 0.00 to disable the function.
Note:
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial
Excitation) as a percentage of E2-03 [Mot No-Load Current].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Short Circuit Braking time at start.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Short Circuit Braking time at stop.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.2 b: APPLICATION
Default
(Range)
0%
(0 - 1000%)
Default
(Range)
0.00 s
(0.00 - 25.50 s)
Default
(Range)
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50
s
(0.00 - 25.50 s)
529
12