12.7 H: TERMINALS
Example Analog Input Settings
• The function set for terminal AI1 is set with FrqBIAS Frq [H3-02 = 4], the gain is 200% [H3-03 = 200.0], and
the bias is 0% [H3-04 = 0.0].
When you input a 10 V signal, the frequency reference will be 200%.
When you input a 5 V signal, the frequency reference will be 100%. Parameter E1-04 [Max Output Frequency]
restricts drive output. When you input a 5 V or more signal, the frequency reference will be 100%.
Figure 12.98 Freq Reference When the Analog Input Gain Setting Is Adjusted
• The function set for terminal AI1 is set with FrqBIAS Frq [H3-02 = 4], the gain is 100% [H3-03 = 100.0], and
the bias is -25% [H3-04 = -25.0].
When you input a 0 V signal, the frequency reference will be -25%.
When H3-01 = 2 [AI1 Signal Level Select = 4 to 20 mA], when you input a 0 V to 2 V signal, the frequency
reference will be 0%. When you input a 2 V to 10 V signal, the frequency reference will be 0% to 100%.
When H3-01 = 1 [-10 to +10V (Bipolar Reference)], it enables signals of positive and negative polarities. When
you input a 0 V to 2 V signal, and the motor rotates in reverse.
Figure 12.99 Frequency Reference When Negative Number Bias Is Configured
Modbus Multi-Function AI1 to 3 Function Selection
Let the MFAI function be assigned to Modbus register 15C1 to 15C3 (Hex.) [Mbus Reg 15C1h through 15C3h
Input Function]. Use H3-40 to H3-42 [15C1h Input Function to 15C3h Input Function] to set the function and use
H3-43 [Mbus In FilterTime Const] to set the input filter.
Register No.
(Hex.)
15C1
15C2
15C3
*1
Set as 100% = 4096.
Figure 12.100 Functional Block Diagram for Modbus Multi-Function AI Command 1
712
Table 12.50 Modbus Multi-Function AI Command Register
Name
15C1h Input Function
15C2h Input Function
15C3h Input Function
*1
Range
-32767 to 32767
-32767 to 32767
-32767 to 32767