11.8 H: TERMINALS
Setting
Function
9
@Regeneration
A
@SpeedLimit
B
@FreqOutput
C
@Standby
D
LO/RE Status
E
EDM Safety
F
SpeedAgree1
10
USpeedAgree1
11
SpeedAgree2
12
USpeedAgree2
13
FreqDetect 1
14
FreqDetect 2
438
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the speed limit is active.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates after the drive stops operating and after the time set with b8-51 [Standby Mode Wait
Time].
ON : The Run command turns on and the magnetic contactor on the input side turns on.
OFF : The Run command turns off and the drive stops operating. Then, the magnetic contactor on the input side
turns off after the time set with b8-51 [Standby Mode Wait Time] elapses.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
OFF : REMOTE
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are off (released).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [SpAgree Det.
Width].
Note:
The drive uses the motor speed as the reference in CLV.
ON : The output frequency is in the range of "frequency reference ± L4-02."
OFF : The output frequency does not align with the frequency reference although the drive is running.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-01 [SpAgree Det.Level] ± L4-02 [SpAgree
Det.Width] and in the range of the frequency reference ± L4-02.
Note:
• The detection function operates in the two motor rotation directions.
• In CLV, the forward/reverse detection level is the value of "Motor Speed ± L4-02."
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the in the range of frequency reference ± L4-
02.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [SpAgree Det.
Width(+/-)].
Note:
The drive uses the motor speed as the reference in CLV and CLV/PM.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-03 [SpAgree Det.Level(+/-)] ± L4-04
[SpAgree Det.Width(+/-)] and in the range of the frequency reference ± L4-04.
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the in the range of frequency reference ± L4-
04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off when the output frequency is higher than the value of L4-01 [SpAgree Det.Level] + L4-02
[SpAgree Det.Width]. After the terminal turns off, the terminal continues to remain off until the output frequency
reaches the level set with L4-01.
Note:
• The detection function operates in the two motor rotation directions. The value of L4-01 is used as the
forward/reverse detection level.
• In CLV, the motor speed is the reference.
ON : The output frequency is less than the value of L4-01 or does not exceed the value of L4-01 + L4-02.
OFF : The output frequency exceeds the value of L4-01 + L4-02.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is higher than the setting value of L4-01 [SpAgree Det.Level].
After the terminal activates, the terminal stays on until the output frequency is at the value of L4-01 - L4-02.
ON : The output frequency is higher than the value of L4-01.
OFF : The output frequency is less than the value of "L4-01 - L4-02", or is less than the value of L4-01.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Ref.
699
699
699
700
700
700
701
701
702
702
703
703