Remove The Control Circuit Terminal Block; Wire A New Drive - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

8.5 Replace the Drive
Screw Size
Screw Shape
M4
Slotted (-)
*1
M5
Slotted (-)
Hex socket cap
(WAF: 5 mm)
M6
Slotted (-)
Hex socket cap
M8
(WAF: 6 mm)
Hex socket cap
M10
(WAF: 8 mm)
*1
When wiring drive models 2056 and 4089 and smaller, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.

Remove the Control Circuit Terminal Block

Remove the keypad and the drive front cover before doing these steps.
1.
Loosen the screws on the control circuit terminal block.
2.
Slide the wired control circuit terminal block down and remove it.

Wire a New Drive

Remove the keypad, front cover, and control circuit terminal block of the new drive. Wire the drive to the main
circuit terminal block before you install a wired control circuit terminal block.
338
Table 8.11 Recommended Wiring Tools
Adapter
Bit
SF-BIT-SL 1,0X4,0-70 PHOENIX CONTACT
Bit
SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
Bit
SF-BIT-HEX 5-50
Bit
SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
Bit
SF-BIT-HEX 6-50
Bit
SF-BIT-HEX 8-50
Figure 8.65 Loosen the Screws
Figure 8.66 Remove the Control Circuit Terminal Block
Bit
Model
Manufacturer
PHOENIX CONTACT
PHOENIX CONTACT
PHOENIX CONTACT
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Torque Driver Model
Torque Wrench
(Tightening Torque)
TSD-M 3NM
-
(1.2 - 3 N∙m)
Wire Gauge ≤
Wire Gauge ≤
2
25 mm
25 mm
(AWG 10):
(AWG 10):
TSD-M 3NM
-
(1.2 - 3 N∙m)
Wire Gauge ≥
Wire Gauge ≥
30 mm
2
30 mm
(AWG 8):
(AWG 8):
-
4.1 - 4.5 N∙m
-
5 - 9 N∙m
-
3 - 3.5 N∙m
-
8 - 12 N∙m
-
12 - 14 N∙m
2
2
*2 *3
*2 *3
*2 *3
*2 *3
*2 *3

Hide quick links: