3.12

Improve the Power Factor

Connect an AC Reactor or a DC Reactor
AC reactors and DC reactors decrease surges in current and improve the power factor on the input side of the
drive.
Connect an AC reactor or a DC reactor to the input side (primary side) in the these conditions:
• To decrease harmonic current or improve the power factor of the power supply
• When there is switching of phase advancing capacitor
• With a large capacity power supply transformer (600 kVA or more).
Note:
• You can use an AC reactor and DC reactor together.
• When you connect a thyristor converter (for example, a DC drive) to the same power supply system, you should use an AC reactor,
regardless of the conditions of the power supply.
• The main circuit terminal block for the drive, and the terminal blocks for the AC and DC reactors come in different shapes. Use caution
when you prepare the ends of the wires.

Connect an AC Reactor

When you connect an AC reactor to the output side (secondary side) of the driver, set C6-02 = 1 [Carrier
Frequency Selection = 2.0 kHz].
A - Power supply
B - MCCB

Connect a DC Reactor

When you install a DC link choke, remove the jumper between terminals +1 and +2. If you will not use a DC link
choke, do not remove the jumper.
A - Power supply
B - MCCB
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
C - AC reactor
D - Drive
Figure 3.57 AC Reactor Connection Example
C - Drive
D - DC reactor
Figure 3.58 DC Reactor Connection Example