12.11 T: AUTOTUNING
■
T4-06 Motor Rated Voltage
No.
Name
(Hex.)
T4-06
Motor Rated Voltage
(3135)
■
T4-07 Motor Rated Current
No.
Name
(Hex.)
T4-07
Motor Rated Current
(3136)
Note:
The value set here becomes the base value for motor protection, the torque limit, and torque control.
■
T4-08 Motor Rated Capacity
No.
Name
(Hex.)
T4-08
Motor Rated Capacity
(3137)
■
T4-09 Motor Poles Number
No.
Name
(Hex.)
T4-09
Motor Poles Number
(3138)
832
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated voltage (V) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the rated current (A) of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated capacity in 0.01 kW units.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
400 V Class: 400.0 V
(400 V Class: 0.0 - 510.0
V)
Default
(Range)
Determined by o2-04 and
C6-01
(10% to 200% of the drive
rated current)
Default
(Range)
Determined by E9-10
(0.10 - 650.00 kW)
Default
(Range)
Determined by E9-01
(2 - 48)