Omron Q2A Series Technical Manual page 709

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

The drive detects FbH [Excessive PID Feedback] when the PID feedback value > b5-36 [PID HiHi Limit Level]
for longer than the time set in b5-37 [PID HiHi Time].
Note:
Refer to "PID Feedback Loss Detection" for more information.
4A: DC Bus Undervolt
Setting
Function
4A
DC Bus Undervolt
ON : The DC bus voltage is less than the setting value of L2-05.
OFF : The DC bus voltage is more than the setting value of L2-05.
4B: FreqRef Loss
Setting
Function
4B
FreqRef Loss
Note:
"L4-05 FrefLoss Det.Selection on page
Refer to
4C: BrkRes Fault
Setting
Function
4C
BrkRes Fault
4D: Motor OL1
Setting
Function
4D
Motor OL1
Note:
Refer to
"L1-01 Motor Cool Type for OL1 Calc on page
4E: Drive PreOH
Setting
Function
4E
Drive PreOH
Note:
"L8-02 Overheat Alm Level on page
Refer to
4F: PreOHTimeLim
Setting
Function
4F
PreOHTimeLim
Note:
"L8-03 Overheat Pre-Alarm Selection on page
Refer to
60: BrkTransFault
Setting
Function
60
BrkTransFault
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the DC bus voltage or control circuit power supply is less than the voltage set with L2-05 [UV
Detection Lvl (Uv1)]. The terminal also turns on when there is a fault with the DC bus voltage.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a loss of frequency reference.
763" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the mounting-type braking resistor is overheating or when there is a braking transistor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the electronic thermal protection value of the motor overload protective function is a minimum of
90% of the detection level.
738" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alm Level].
774" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when L8-03 = 4 [Overheat Pre-Alarm Selection = Run@L8-19 Rate] and oH [Heatsink Overheat] does
not clear after the drive decreases the frequency for 10 cycles.
774" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the internal braking transistor overheats and the drive detects an rr [Dynamic Braking Transistor
Fault] fault.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
12.7 H: TERMINALS