Omron Q2A Series Technical Manual page 650

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.6 F: OPTIONS
F6-16 Gateway Mode
No.
Name
(Hex.)
F6-16
Gateway Mode
(0B8A)
0 : Disabled
1 : 1 Slave Drive
2 : 2 Slave Drives
3 : 3 Slave Drives
4 : 4 Slave Drives
Gateway Mode processes communications through internal the RS-485 communication function to relay data
from a drive that has the communication option to more than one drive that does not have the communication
option. This function lets you use fieldbus communication to connect a maximum of 5 drives with only one
communication option. The drive sends these commands and responses between the controller (Host device),
master drive (Drive 0), and the slave drives (Drive 1 to Drive 4).
• Commands: Run command and frequency reference
• Output frequency and drive status (during run, faults)
• Read and write parameters
• Read monitors
NOTICE: When you use Gateway Mode, do not install the communication option in slave drives. Failure to obey can cause
problems with synchronization of drive commands and responses.
Note:
• Response speed with the communication option is slower than with point-to-point communications.
• Set H5-03 [Communication Parity Selection] to the same value on the master drive and slave drives.
Table 12.36
shows the parameter settings when you connect 4 slave drives:
F6-16
[Gateway
Mode]
Drive0
1 - 4
(Master Drive)
Drive1
0
(Slave Drive 1)
Drive2
0
(Slave Drive 2)
Drive3
0
(Slave Drive 3)
Drive4
0
(Slave Drive 4)
*1
Set the number of connected slave drives.
*2
Make sure that you set the communications speed and communications parity to the same value on the master drive and slave drives.
*3
To correctly detect the response timeout, do not change the value of H5-06 from the default value.
*4
Set H5-09 ≥ 0.9 s. When H5-09 < 0.9, the drive will detect CE before it detects a response timeout.
*5
Set the Run command and frequency reference source on slave drives to Modbus communications.
650
V/f
CL-V/f
OLV
CLV
Sets the gateway mode operation and the number of connected slave drives.
Table 12.36 Parameter Settings to Connect 4 Slave Drives
H5-01
H5-02
[Mbus
[Mbus
Address]
BaudRate]
*2
1F (Default)
*2
01
*2
02
*2
03
*2
04
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
H5-06
H5-03
[Mbus Tx Wait
[Mbus Parity]
Time]
*2
*3
5 ms
*2
*3
5 ms
*2
*3
5 ms
*2
*3
5 ms
*2
*3
5 ms
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
H5-09
b1-01
[Mbus CE
[Freq. Ref. Sel.
Detect Time]
1]
*4
2.0 s minimum
3 [Option PCB]
2 [Modbus
*4
0.9 s minimum
Communications]
*5
2 [Modbus
*4
0.9 s minimum
Communications]
*5
2 [Modbus
*4
0.9 s minimum
Communications]
*5
2 [Modbus
*4
0.9 s minimum
Communications]
*5
Default
(Range)
0
(0 - 4)
b1-02
[Run Comm.
Sel 1]
3 [Option PCB]
2 [Modbus
Communications]
*5
2 [Modbus
Communications]
*5
2 [Modbus
Communications]
*5
2 [Modbus
Communications]
*5