Omron Q2A Series Technical Manual page 805

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Trend Plot Display
A - Select Ux-xx [MONITORS]
(Monitor 1) with o1-24.
B - Select Ux-xx [MONITORS]
(Monitor 2) with o1-25.
C - Set the maximum value of
Monitor 2 with o1-50
D - Set the minimum value of Monitor
2 with o1-49
o1-02 Mon.Sel@Power-Up
No.
Name
(Hex.)
o1-02
Mon.Sel@Power-Up
(0501)
RUN
1 : FreqReference (U1-01)
2 : Direction
3 : OutFrequency (U1-02)
4 : OutCurrent (U1-03)
5 : User Monitor (o1-01)
Shows the monitor item selected in o1-01 [User Monitor Selection].
o1-03 FrqDisplay Unit Selection
No.
Name
(Hex.)
o1-03
FrqDisplay Unit Selection
(0502)
Note:
When you change ths parameter, these monitor and parameter units also change:
• U1-01 [Frequency Reference]
• U1-02 [Output Frequency]
• U1-05 [Motor Speed]
• U1-16 [SFS Output Frequency]
• d1-01 to d1-17 [Reference 1 to Jog Reference]
0 : 0.01 Hz
1 : 0.01% (100%=E1-04)
The maximum output frequency is 100%.
2 : rpm
The drive uses the maximum output frequency and number of motor poles calculate this value automatically.
Note:
When you use this setting, make sure that you set the number of motor poles in these parameters:
• E2-04 [Motor Pole Count]
• E4-04 [M2 Pole Count]
• E5-04 [PM Mot Pole Count]
• E9-08 [Motor Pole Count]
3 : User-selected units
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
G
F
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor item that the keypad screen shows after energizing the drive. Refer to "U:
Monitors" for information about the monitor items that the keypad screen can show. This
parameter is only available when using an LED keypad.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the display units for the frequency reference and output frequency.
E - Set the time scale with o1-51
F - Set the minimum value of Monitor
1 with o1-47
G - Set the maximum value of
Monitor 1 with o1-48
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.10 o: KEYPAD
Default
(Range)
1
(1 - 5)
Default
(Range)
Determined by A1-02
(0 - 3)
12
805