Omron Q2A Series Technical Manual page 437

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

No.
Name
(Hex.)
H2-65
3NO-3CM Dly Time
(1B4B)
Expert
H2-66
4NO-4CM 2nd Function
(1B4C)
Expert
H2-67
4NO-4CM Logic
Operation
(1B4D)
Expert
H2-68
4NO-4CM Dly Time
(1B4E)
Expert
H2-xx: MFDO Function Selections
Setting
Function
0
Through Mode
1
Drive Ready
2
Drive Enable
3
Fault
4
Alarm
5
@Run
6
@Reverse
7
Zero Speed
8
ZeroServo ok
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum on time used to output the logical calculation results from terminal
3NO-3CM.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the second function for terminal 4NO-4CM. The logical calculation results of
the terminals assigned to functions by H2-03 [4NO-4CM Funct Selection] is output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the logical operation for the functions set in H2-03 [4NO-4CM Funct Selection]
and H2-66 [4NO-4CM 2nd Function].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum on time used to output the logical calculation results from terminal
4NO-4CM.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via Modbus or the communication option. This signal does not function if signals from the PLC are not
configured.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive is ready and running.
V/f
CL-V/f
OLV
CLV
AOLV
This terminal activates when the H1-xx = 1A [Drive Enable] terminal activates.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a fault.
Note:
The terminal will not turn on for CPF00 and CPF01 [Control Circuit Error] faults.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive detects a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the Run command is input and when the drive is making voltage.
ON : Drive is running
OFF : Drive is stopping
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is less than the value of E1-09 [Min Output Frequency] or b2-01
[ZSpd/DCI Threshold].
Note:
A1-02 [Control Method] selects which parameter is the reference.
A1-02 Setting
Control Method
0
V/f Control
1
PG V/f Control
2
OLVector
3
CLVector
4
Adv OLVector
5
PM OLVector
6
PM AOLVector
7
PM CLVector
8
EZ Vector
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency ≥ value of E1-09 or b2-01.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when positioning in the range set with b9-02 [Zero Servo Width for Completion] completes
after sending the Zero-Servo command.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Parameter Used as the Reference
E1-09
E1-09
b2-01
E1-09
E1-09
E1-09
E1-09
b2-01
E1-09
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: TERMINALS
Default
Ref.
(Range)
0.1 s
696
(0.0 - 25.0 s)
0
696
(0 - A7)
1
696
(1 - 9)
0.1 s
697
(0.0 - 25.0 s)
Ref.
697
697
697
697
697
697
698
698
699
437
11