4.4
Items to Check before Starting Up the Drive
◆
Check before Energizing the Drive
Check these items before energizing the drive.
Items to Check
Input Power Supply Voltage
Connection between Drive Output
Terminals and Motor Terminals
Control Circuit Terminal Wiring
Control Circuit Terminal Status
Connection between Machinery and
Motor
◆
Check after Energizing the Drive
Check these items after energizing the drive. The keypad will show these screens depending on the drive status.
Status
During Usual
Operation
When the Drive
Detects a Fault
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Table 4.4 Items to Check before Energizing the Drive
The voltage of the input power supply must be:
400 V class: three-phase AC 380 V to 480 V 50/60 Hz, DC 510 V to 680 V
Correctly and safely wire power supply input terminals R/L1, S/L2, T/L3.
Correctly ground the drive and motor.
Correctly wire drive output terminals (U/T1, V/T2, and W/T3) and motor terminals (U, V, and W), and tighten loose screws.
Turn OFF the inputs from all devices and switches connected to the drive control circuit terminals.
Turn OFF the inputs from all devices and switches connected to the drive control circuit terminals.
Disengage all couplings and belts that connect the motor and machinery.
Table 4.5 Display Status after Energizing the Drive
Display
The data display area will show the HOME screen
HOME Screen
The display changes depending on the fault. Refer to "Troubleshooting" to remove the cause of the fault.
Note:
If the screen shows a different screen, do these steps to show the fault content again:
1.
2.
4.4 Items to Check before Starting Up the Drive
Description
Description
will illuminate.
Push
from the HOME screen.
Push
(Home) from a different screen than the HOME screen.
4
127