Omron Q2A Series Technical Manual page 551

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

b5-38 PID SP User Scale for Display
No.
Name
(Hex.)
b5-38
PID SP User Scale for
Display
(01FE)
The drive uses this parameter and b5-39 [PID SP User digits for Display] together.
When b5-20 = 4 [PID Unit Selection = ], the drive applies user-set PID setpoint and display units to U5-01 [PID
Feedback] and U5-04 [PID Setpoint].
b5-39 PID SP User digits for Display
No.
Name
(Hex.)
b5-39
PID SP User digits for
Display
(01FF)
The drive uses this parameter and b5-38 [PID SP User Scale for Display] together.
When parameter b5-20 = 4 [PID Unit Selection = ], the drive applies user-set PID setpoint and display units to
U5-01 [PID Feedback] and U5-04 [PID Setpoint]
0 : No Decimal Places
1 : 1 Decimal Place
2 : 2 decimal places
3 : 3 Decimal Places
b5-40 Fref Mon@PID
No.
Name
(Hex.)
b5-40
Fref Mon@PID
(017F)
0 : U1-01 with PID Output
Monitor U1-01 shows the frequency reference that was increased or decreased by the PID output.
1 : U1-01 without PID Output
Monitor U1-01 shows the actual frequency reference.
b5-47 PID Out Rev Operation Mode
No.
Name
(Hex.)
b5-47
PID Out Rev Operation
Mode
(017D)
Set b5-01 = 3 or 4 [PID Enable = Fref + PID Trim, Fref + PID Trim (D on feedback)] to enable this parameter.
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse.
b5-53 PID I Ramp Limit
No.
Name
(Hex.)
b5-53
PID I Ramp Limit
(0B8F)
RUN
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the display for U5-01, U5-04 when the drive operates at the maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of digits to set and show the PID setpoint.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the contents for monitor U1-01 [Frequency Reference] in PID control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets reverse motor rotation when the PID control output is negative.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of PID control when the PID feedback changes quickly.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.2 b: APPLICATION
Default
(Range)
Determined by b5-20
(1 - 60000)
Default
(Range)
2
(0 - 3)
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
Default
(Range)
0.0 Hz
(0.0 - 10.0 Hz)
551
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents