oPE05
Run Cmd/Freq Ref Source Sel Err
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Causes
These commands are set in Digital Inputs (H1-xx,
F3-10 to F3-25, and H7-01 to H7-04) at the same
time:
• Setting values 67 [SpeedSearch Fmax] and 68
[SpeedSearch Fref]
• Setting values 40, 41, 42, 43 [KEB Thru1 NC,
KEB Thru1 NO, KEB Thru2 NC, KEB Thru2
NO] and 32 [HiSlipBraking]
• Setting values 61 [Motor 2 Select] and 19 [Ac/
Dec Time2]
• Setting values 40, 41 [KEB Thru1 NC, KEB
Thru1 NO] and 42, 43 [KEB Thru2 NC, KEB
Thru2 NO]
• Setting values 1, 2 [Forward Run, Reverse Run]
and 3, 4 [Run Command, FWD/REV Cmd]
• Setting values 30 [DCInj Cmd] and 1A [Drive
Enable]
• Setting values 61 [Motor 2 Select] and 65, 66
[Up2 Command, Dw2 Command]
Settings for N.C. and N.O. input [H1-xx] for these
functions were selected at the same time:
• Setting value 34 [Fast Stop NO]
• Setting value 35 [Fast Stop NC]
These settings were entered while H1-xx = 9 [Ext
Ref 1/2]:
• b1-15 = 4 [Freq. Ref. Sel. 2 = Pulse Train Input]
• H6-01 ≠ 0 [PI Pulse Train Function ≠ Freq Ref]
These settings were entered while H1-xx = 9 [Ext
Ref 1/2]:
• b1-15 = 3 [Option PCB] or b1-16 = 3 [Run
Comm. Sel 2 = Option PCB]
• No option card is connected to the drive.
These settings were entered while H1-xx = 9 [Ext
Ref 1/2]:
• b1-15 = 1 [Analog Input]
• H3-02 ≠ 0 [AI1 Function Selection ≠ Frequency
Reference] or H3-10 ≠ 0 [AI2 Function Selection
≠ ]
These parameters are set at the same time:
• H1-xx ≠ 1A [Drive Enable]
• H2-xx = 2 [Drive Enable]
These parameters are set at the same time:
• H6-01 ≠ 3 [PG Feedback]
• H1-xx = 15 [FWD/REV Det]
The following parameters are set at the same time:
• H1-xx = 65/66 [Up2 Command/Dw2 Command]
• H3-01, H3-05, H3-09 = 1 [AI1 Signal Level
Select, AI3 Signal Level Select, AI2 Signal Level
Select = -10 to +10V (Bipolar Reference)]
These settings do not agree:
• A PG-RT3 option is connected to the drive.
• H1-xx = 61 [Motor 2 Select] is set.
Causes
The setting to assign the Run command or
frequency reference to an option card or the pulse
train input is incorrect.
b1-01 = 3 [Freq. Ref. Sel. 1 = Option PCB] is set,
but there is no option card connected to the drive.
b1-02 = 3 [Run Comm. Sel 1 = Option PCB] is set,
but there is no option card connected to the drive.
The following parameters are set at the same time:
• b1-01 = 4 [Pulse Train Input]
• H6-01 ≠ 0 [PI Pulse Train Function ≠ Freq Ref]
7.6 Parameter Setting Errors
Possible Solutions
Remove the function settings that are not in use.
Remove one of the function settings.
Set H6-01 = 0
Connect an input option card to the drive.
Set H3-02 = 0 or H3-10 = 0.
Set the parameters correctly.
Set the parameters correctly.
Remove one of the function settings.
Set the parameter correctly.
Note:
The Motor Switch function is not available with the PG-RT3
option.
Possible Solutions
Correct the parameter settings.
Connect an option card to the drive.
Set H6-01 = 0.
7
285