Omron Q2A Series Technical Manual page 729

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

H5-17 ENTER@CPU Busy Response
No.
Name
(Hex.)
H5-17
ENTER@CPU Busy
Response
(11A1)
Expert
1 : Ignore (No Write)
2 : Write RAM Only
H5-18 Mbus Speed Filter over Comms
No.
Name
(Hex.)
H5-18
Mbus Speed Filter over
Comms
(11A2)
Sets the filter time constant when you monitor the output frequency or motor speed during Modbus
communications or use of the communication option.
These are the Modbus registers:
• 003EH (Output Frequency)
• 003FH (Output Frequency)
• 0044H (U1-05: Motor Speed)
• 00ACH (U1-05: Motor Speed)
• 00ADH (U1-05: Motor Speed)
H5-20 Mbus Par Reload Mode
No.
Name
(Hex.)
H5-20
Mbus Par Reload Mode
(0B57)
1 : Reload@Power Cycle
2 : Reload Now
Note:
• The setting value automatically returns to H5-20 = 1 after you enable Modbus communications parameter changes.
• The setting values of these parameters are enabled:
–H5-01 [Mbus Address]
–H5-02 [Mbus BaudRate]
–H5-03 [Mbus Parity]
–H5-06 [Mbus Tx Wait Time]
H5-25 Mbus 5A Reg1 Selection
No.
Name
(Hex.)
H5-25
Mbus 5A Reg1 Selection
(1589)
RUN
H5-26 Mbus 5A Reg2 Selection
No.
Name
(Hex.)
H5-26
Mbus 5A Reg2 Selection
(158A)
RUN
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation when the EEPROM write command is sent without EEPROM write available.
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant used when monitoring motor speed during Modbus communications
or with a communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to immediately enable updated Modbus communications parameters.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified Modbus communications register when responding to the
master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified Modbus communications register when responding to the
master device.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 H: TERMINALS
Default
(Range)
1
(1, 2)
Default
(Range)
0 ms
(0 - 100 ms)
Default
(Range)
1
(1, 2)
Default
(Range)
0044H (U1-05)
(0000H - FFFFH)
Default
(Range)
0045H (U1-06)
(0000H - FFFFH)
729