F4-04 Term.V2 Gain
No.
Name
(Hex.)
F4-04
Term.V2 Gain
(0394)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Term.V2 Level of Signal] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V2 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V2
outputs a maximum voltage of 10 V.
• F4-03 [Term.V2 Function Selection] = 103 (U1-03: Output Current)
• F4-04 = 50.0%
• F4-06 [Term.V2 Bias] = 0.0%
• F4-08 = 0 (0 to 10V)
F4-05 Term.V1 Bias
No.
Name
(Hex.)
F4-05
Term.V1 Bias
(0395)
RUN
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Term.V1 Level of Signal] to set the
signal level.
F4-06 Term.V2 Bias
No.
Name
(Hex.)
F4-06
Term.V2 Bias
(0396)
RUN
The maximum output voltage output from terminal V2 is ±10 V. Use F4-08 [Term.V2 Level of Signal] to set the
signal level.
F4-07 Term.V1 Level of Signal
No.
Name
(Hex.)
F4-07
Term.V1 Level of Signal
(0397)
0 : 0 to 10V
1 : -10 to 10V
F4-08 Term.V2 Level of Signal
No.
Name
(Hex.)
F4-08
Term.V2 Level of Signal
(0398)
0 : 0 to 10V
1 : -10 to 10V

F5: DIGITAL OUTPUT

F5 parameters set the output mode and function of output signals when you use digital output option card DO-A3.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from terminal V2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V1. Set the level of the analog signal
sent from the V1 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from terminal V2. Set the level of the analog signal
sent from the V2 terminal at 10 V or 20 mA as 100% when an output for monitoring items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output signal level for terminal V2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.6 F: OPTIONS
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
12
643