7.6 Parameter Setting Errors

7.6

Parameter Setting Errors

Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values
are not correct. Refer to the table in this section, examine the parameter setting that caused the error, and remove
the cause of the error. You must first correct the parameter setting errors before you can operate the drive. The
drive will not send notification signals for the faults and alarms when these parameter setting errors occur.
Code
Name
oPE01
Drive Capacity Setting Error
Code
Name
oPE02
Parameter Range Setting Error
Code
Name
oPE03
Multi-Function Input Setting Err
284
Causes
The value set in o2-04 [Drive KVA Selection] does
not agree with the drive model.
Causes
Parameters settings are not in the applicable setting
range.
Set E2-01 ≤ E2-03 [Mot Rated Current (FLA) ≤
Mot No-Load Current].
Causes
The settings for these parameters do not agree:
• Terminal DI1 to DI8 Function Selection H1-01
to H1-08
• Terminal D1 to DF Function Selection F3-10 to
F3-25
• Virtual Multi-Function Inputs 1 to 4 H7-01 to
H7-04
The settings for the standby mode function do not
agree:
• b8-50 = 0 [Standby Mode Selection = Disabled]
and H2-xx: MFDO Function Select = C
[@Standby]
• b8-50 = 1 [Enabled] and H2-xx ≠ C
The settings for MFDIs overlap.
Note:
This does not include H1-xx: MFDI Function
Select = 20 to 2F [External Fault] and
[Reserved].
These pairs of MFDI functions are not set to Digital
Inputs (H1-xx, F3-10 to F3-25, and H7-01 to H7-
04) at the same time:
• Setting values 62 [Up Command] and 63 [Down
Command]
• Setting values 65 [Up2 Command] and 66 [Dw2
Command]
• Setting values 3 [Run Command] and 4 [FWD/
REV Cmd]
A minimum of two of these MFDI combinations are
set to Digital Inputs (H1-xx, F3-10 to F3-25, and
H7-01 to H7-04) at the same time:
• Setting values 62 [Up Command] and 63 [Down
Command]
• Setting values 65 [Up2 Command] and 66 [Dw2
Command]
• Setting values 17 [Ac/Dec Hold]
• Setting values 16 [Ref Sample]
• Setting values E to 10 [Add Offset Frequency 1
to 3 (d7-01 to d7-03)]
These PID settings are enabled at the same time.
• b5-01 [PID Enable]
• H1-xx = 62 [Up Command]
• H1-xx = 63 [Down Command]
Possible Solutions
Set o2-04 to the correct value.
Possible Solutions
1.
Push
to show U1-18 [oPE Fault Parameter], and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx
errors have priority over oPE02.
Make sure that E2-01 > E2-03.
Note:
If it is necessary to set E2-01 < E2-03, first lower the value
set in E2-03, and then set E2-01.
Possible Solutions
Set the parameters correctly.
Set the parameters correctly.
Set the parameters correctly to prevent MFDI function overlap.
Set the MFDI pairs.
Remove the function settings that are not in use.
• Set b5-01 = 0 [Disabled].
• Remove the function Up/Down command settings.