Omron Q2A Series Technical Manual page 179

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Model
Terminals
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
U/T1, V/T2, W/T3
4675
-, +1
+3
*1
For IP20 protection, use wires that are in the range of applicable gauges.
*2
Remove insulation from the ends of wires to expose the length of wire shown.
*3
For wire gauges more than 30 mm
*4
Install an RCM/RCD with this wire gauge to maintain compliance with IEC/EN 61800-5-1:2007.
*5
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*6
A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.
Connect a Fuse to the Input Side (Primary Side)
The drive circuit protection must comply with IEC/EN 61800-5-1:2007 for protection against a short circuit in the
internal circuitry. The manufacturer recommends connecting semiconductor protection fuses on the input side for
branch circuit protection.
WARNING! Electrical Shock Hazard. Do not immediately energize the drive or operate peripheral devices after the drive blows
a fuse or trips an RCM/RCD. Wait for the time specified on the warning label at a minimum and make sure that all indicators are
OFF. Then check the wiring and peripheral device ratings to find the cause of the problem. Contact the manufacturer before
energizing the drive or peripheral devices if the cause is not known. Failure to obey can cause death or serious injury and
damage to the drive.
*1
The manufacturer recommends a fuse with a large rated current for applications with repeated loads.
Table 5.2 Factory-Recommended Branch Circuit Protection (400 V Class)
Semiconductor Protection Fuse Rated Current
Drive Model
Manufacturer: EATON/Bussmann
4002
4004
4005
4007
4009
4012
4018
4023
4031
4038
4044
4060
4075
4089
*1
A fuse with a large rated current for applications with repeated loads is recommended.
CE Standards Compliance for DC Power Supply Input
To comply with CE Standards, install a fuse for the DC power supply input.
Example for a DC power supply that has two drives connected in parallel.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Applicable Gauge
Recommended
(IP20 Applicable
Gauge
*1
Gauge
)
2
mm
2
mm
70 - 150 × 4P
120 × 4P
(150 × 4P)
70 - 150 × 4P
95 × 4P
(120 - 150 × 4P)
95 - 185 × 4P
95 × 4P
(185 × 4P)
35 - 95 × 4P
70 × 4P
(95 × 4P)
60 - 150
95 × 2P
(-)
2
, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lb.∙in. to 40 lb.∙in.).
FWH-50B
FWH-50B
FWH-50B
FWH-60B
FWH-60B
FWH-60B
FWH-80B
FWH-90B
FWH-150B
FWH-200B
FWH-200B
FWH-225A
FWH-250A
FWH-275A
5.2 European Standards
Terminal Screw
Wire
Stripping
*2
Length
Size
Shape
mm
-
M12
Hex self-locking nut
-
M12
Hex self-locking nut
-
M12
Hex self-locking nut
-
M12
Hex self-locking nut
-
M12
Hex bolt (slotted)
Semiconductor Protection Fuse Rated Current
Drive Model
Manufacturer: EATON/Bussmann
4103
4140
4168
4208
4250
4296
4371
4389
4453
4568
4675
Tightening Torque
N∙m (lb.∙in.)
35
(310)
35
(310)
35
(310)
35
(310)
32 - 40
(283 - 354)
FWH-275A
FWH-300A
FWH-325A
*1
FWH-400A
FWH-500A
FWH-600A
FWH-700A
FWH-800A
FWH-1000A
FWH-1200A
FWH-1200A
FWH-1400A
*1
FWH-1600A