Commissioning

5.2 Preparing for commissioning

5.2
Preparing for commissioning
5.2.1

Collecting motor data

Before starting commissioning, you must know the following data:
● Which motor is connected to the inverter?
Note down the Article No. of the motor and the motor's nameplate data.
If available, note down the motor code on the motor's nameplate.
● In which region of the world is the motor to be used?
- Europe IEC: 50 Hz [kW]
- North America NEMA: 60 Hz [hp] or 60 Hz [kW]
● How is the motor connected?
Pay attention to the connection of the motor (star connection [Y] or delta connection [Δ]).
Note the appropriate motor data for connecting.
5.2.2

Factory setting of the converter control

Motor
In the factory, the inverter is set for an induction motor matching the rated power of the
Power Module.
Inverter control
You can find the factory setting of the inverter control in Chapter: Factory setting of the
interfaces (Page 86)