Electromagnetic Compatibility Of Variable-Speed Drives - Siemens SINAMICS G120 PM240P-2 Installation Manual

Frequency converters
Table of Contents

Advertisement

Technical data

6.8 Electromagnetic compatibility of variable-speed drives

6.8
Electromagnetic compatibility of variable-speed drives
EMC (electromagnetic compatibility) means that the devices function satisfactorily without
interfering with other devices and without being disrupted by other devices. EMC applies
when the emitted interference (emission level) and the interference immunity are matched
with each other.
The product standard IEC/EN 61800-3 describes the EMC requirements placed on
"Variable-speed drive systems".
A variable-speed drive system (or Power Drive System PDS) consists of the converter as
well as the associated electric motors and encoders including the connecting cables.
The driven machine is not part of the drive system.
Note
PDS as component of machines or systems
When you install PDS into machines or systems, additional measures may be required so
that the product standards of these machines or systems is complied with. The machine or
system builder is responsible for taking these measures.
Environments and categories
Environments
IEC/EN 61800-3 makes a distinction between the "first environment" and "second
environment" - and defines different requirements for these environments.
● First environment:
Residential buildings or locations at which the PDS is directly connected to a public low-
voltage supply without intermediate transformer.
● Second environment:
All industrial plant/systems or locations that are connected to the public grid through their
own, dedicated transformer.
Categories
IEC/EN 61800-3 makes a distinction between four drive system categories:
● Category C1:
Drive systems for rated voltages < 1000 V for unrestricted use in the "first environment"
● Category C2:
Stationary PDS for rated voltages < 1000 V for operation in the "second environment".
Appropriately qualified personnel are required to install the PDS. An appropriately trained
and qualified person has the necessary experience for installing and commissioning a
PDS, including the associated EMC aspects.
Additional measures are required for operation in the "first environment".
72
Hardware Installation Manual, 06/2020, A5E37800827C AD
Power Module PM240P-2

Advertisement

Table of Contents
loading