Identifying The Motor Data And Optimizing The Closed-Loop Control - Siemens SINAMICS G120C USS/MB Operating Instructions Manual

Sinamics g120c series low voltage converter built-in units with frame sizes aa - f
Hide thumbs Also See for SINAMICS G120C USS/MB:
Table of Contents

Advertisement

5.4.6

Identifying the motor data and optimizing the closed-loop control

The inverter has several techniques to automatically identify the motor data and optimize the
speed control.
To start the motor data identification routine, you must switch-on the motor via the terminal
strip, fieldbus or from the operator panel.
Unexpected machine motion when the motor data identification is active
For the stationary measurement, the motor can make several rotations. The rotating
measurement accelerates the motor up to its rated speed. Secure dangerous machine parts
before starting motor data identification:
● Before switching on, ensure that nobody is working on the machine or located within its
● Secure the machine's work area against unintended access.
● Lower hanging/suspended loads to the floor.
Requirements
● You selected a method of motor data identification during quick commissioning, e.g.
measuring motor data while the motor is stationary.
When quick commissioning is complete, the inverter issues alarm A07991.
● The motor has cooled down to the ambient temperature.
An excessively high motor temperature falsifies the motor data identification results.
Procedure when using the BOP-2 operator panel
To start the motor data identification, proceed as follows:
Press the HAND/AUTO key.
The BOP-2 displays the symbol indicating manual operation.
Switch on the motor.
During motor data identification, "MOT-ID" flashes on the BOP‑2.
If the inverter again outputs alarm A07991, then it waits for a new ON command to start the
rotating measurement.
If the inverter does not output alarm A07991, switch off the motor as described below, and
switch over the inverter control from HAND to AUTO.
Switch on the motor to start the rotating measurement.
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
WARNING
working area.
5.4 Quick commissioning using the BOP-2 operator panel
Commissioning
133

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120c dpSinamics g120c pn

Table of Contents