11.98
14.1
Power reduction at increased coolant temperature
The rated current must be reduced according to Figure 14.2 for cooling medium temperatures exceeding 40°C.
Cooling medium temperatures > 50°C are not permissible.
permissible rated current
in %
100
90
80
75
70
60
10
20
30
Figure 14.2
Maximum permitted rated current depending on coolant temperature
14.2
Power reduction at altitudes > 1000m above MSL
The rated current must be reduced as shown in Figure 14.3 in the event of installation altitudes > 1000 m above
mean sea level. Installation altitudes > 2000 m above MSL (please enquire)
permissible rated current
in %
100
90
80
70
60
0
1000
2000
Figure 14.3
Maximum values for rated current and rated voltage depending on installation altitude
Siemens AG
6SE7087-6AC85-0AA0
Common Rectifier
Operating instructions
Coolant temperature
in °C
40
50
3000
4000
Installation altitude
in m above sea level
permissible rated current
in %
100
90
80
70
60
0
1000
2000
Technical data
3000
4000
Installation altitude
in m above sea level
14-3