9.2

Pulse frequency and current reduction

Pulse frequency and current reduction
Table 9- 3
Power
rating at
400 V
kW
0.75
1.5
3
4
5.5
7.5
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Current reduction depending on pulse frequency
Frame
Inverter
Output current at pulse frequency of
size
current
rating
at 4 kHz
6 kHz
A
A
A
2.2
1.9
A
4.1
3.5
B
7.7
6.5
C
10.2
8.7
C
13.2
11.2
C
19
16.2
9.2 Pulse frequency and current reduction
8 kHz
10 kHz
12 kHz
A
A
A
1.5
1.3
1.1
2.9
2.5
2.1
5.4
4.6
3.9
7.1
6.1
5.1
9.2
7.9
6.6
13.3
11.4
9.5
Technical data
14 kHz
16 kHz
A
A
1.0
0.9
1.8
1.6
3.5
3.1
4.6
4.1
5.9
5.3
8.6
7.6
211