Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[2]
PM, salient IPM
[5]
SynRM
[6]
PMaSynRM
1-11 Motor Model
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Automatically sets the factory values for the selected motor. If the default value [1] Std. Asynchron is used, determine settings manually
according to the selection in parameter 1-10 Motor Construction.
There are no models available for SynRM motors.
Option
Name
[1]
Std. asynchron
[2]
Std. PM, non salient
[3]
Std. PM salient
[10]
Danfoss OGD LA10
[11]
Danfoss OGD V210
1-14 Damping Gain
Default value:
Size related
Setup:
All setups
Data type:
Int16
90
| © 2024.09
Description
This option is only available in FC 302.
Use for IPM motors, interior-mounted magnet. PM motors are
divided into 2 groups, with either surface-mounted (SPM)/non-
salient magnets or interior-mounted (IPM)/ salient magnets.
Use for SynRM, synchronous reluctance motors.
Use for PMaSynRM, Permanent Magnet assisted synchronous
reluctance motors.
Parameter type:
Conversion index:
Change during operation:
NOTICE
Description
Default motor model when [0] Asynchron is selected in
parameter 1-10 Motor Construction.
Selectable when [1] PM, non-salient SPM is selected in parameter
1-10 Motor Construction.
Selectable when [1] PM, non-salient SPM is selected in parameter
1-10 Motor Construction. Only available for T5 in 1.5–3 kW.
Settings are loaded automatically for this specific motor.
Selectable when [1] PM, non-salient SPM is selected in parameter
1-10 Motor Construction. Only available for T5 in 0.75–3 kW.
Settings are loaded automatically for this specific motor.
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
NOTICE
Option
–
False
Range, 0 - 250%
0
True
AU275636650261en-003201 / 130R0334