Programming Guide | VLT® AutomationDrive FC 301/FC 302
Setup:
1 setup
Data type:
Uint8
Select the time base to be associated with the preventive maintenance event.
Option
Name
[0]
Disabled
[1]
Running hours
[2]
Operating hours
[3]
Date & time
[4]
No of counts
23-13 Maintenance Interval
Default value:
1
Setup:
1 setup
Data type:
Uint32
Set the interval associated with the current preventive maintenance event. This parameter is only used if [1] Running Hours or [2]
Operating Hours is selected in parameter 23-12 Maintenance Base. The timer is reset in parameter 23-15 Reset Maintenance Word.
23-14 Maintenance Date and Time
Default value:
Size related
Setup:
1 setup
Data type:
TimeOfDay
Set the date and time for the next maintenance occurrence if the preventive maintenance event is based on date/time. Date format
depends on the setting in parameter 0-71 Date Format while the time format depends on the setting in parameter 0-72 Time Format.
The drive has no back-up of the clock function. The set date/time is reset to default (2000-01-01 00:00) after a power-down. In
parameter 0-79 Clock Fault, it is possible to program a warning if the clock has not been set properly, for example after a power-
down. Set the time at least 1 hour later than actual time.
When mounting a VLT® Analog I/O option MCB 109 option card, a battery back-up of the date and time is included.
626
| © 2024.09
Conversion index:
Change during operation:
Description
Disables the preventive maintenance event.
The number of hours the motor has run. Running hours are not
reset at power-on. Specify the maintenance time interval in
parameter 23-13 Maintenance Interval.
The number of hours the drive has run. Operating hours are
not reset at power-on. Specify the maintenance time interval in
parameter 23-13 Maintenance Interval.
Uses the internal clock. Specify the date and time of the next
maintenance occurrence in parameter 23-14 Maintenance Date
and Time.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
NOTICE
NOTICE
Parameter Descriptions
–
True
Range, 1 - 2147483647, Array
[6]
0
True
Range, 0 - 0, Array [6]
0
True
AU275636650261en-003201 / 130R0334