Programming Guide | VLT® AutomationDrive FC 301/FC 302
10-01 Baud Rate Select
Default value:
–
Setup:
2 setups
Data type:
Uint8
Select the fieldbus transmission speed. The selection must correspond to the transmission speed of the master and of the other fieldbus
nodes.
Option
Name
[16]
10 Kbps
[17]
20 Kbps
[18]
50 Kbps
[19]
100 Kbps
[20]
125 Kbps
[21]
250 Kbps
[22]
500 Kbps
10-02 MAC ID
Default value:
Size related
Setup:
2 setups
Data type:
Uint8
Select the station address. Every station connected to the same network must have an unambiguous address.
10-05 Readout Transmit Error Counter
Default value:
0
Setup:
All setups
Data type:
Uint8
View the number of CAN control transmission errors since the last power-up.
10-06 Readout Receive Error Counter
Default value:
0
Setup:
All setups
Data type:
Uint8
View the number of CAN control receipt errors since the last power-up.
10-07 Readout Bus Off Counter
Default value:
0
374
| © 2024.09
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Parameter Descriptions
Option
–
True
Range, 1 - 127 N/A
0
True
Range, 0 - 255
0
True
Range, 0 - 255
0
True
Range, 0 - 255
AU275636650261en-003201 / 130R0334