Programming Guide | VLT® AutomationDrive FC 301/FC 302
Ref./Feedback
[RPM]
Par 6-xx
1500
'High Ref./
Feedb. Value'
1200
900
600
300
Par 6-xx
'Low Ref./
150
Feedb. Value'
Ex.
1 V
Par 6-xx
'Low Voltage'or
'Low Current'
Figure 73: Analog Input 1
6-10 Terminal 53 Low Voltage
Default value:
Size related
Setup:
All setups
Data type:
Int16
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in parameter 6-14
Terminal 53 Low Ref./Feedb. Value.
6-11 Terminal 53 High Voltage
Default value:
10 V
Setup:
All setups
Data type:
Int16
Enter the high voltage value. This analog input scaling value should correspond to the high reference feedback value set in parameter
6-15 Terminal 53 High Ref./Feedb. Value.
6-12 Terminal 53 Low Current
Default value:
0.14 mA
Setup:
All setups
Data type:
Int16
Enter the low current value. This reference signal should correspond to the minimum reference value, set in parameter 3-02 Minimum
Reference. Set the value to exceed 2 mA to activate the live zero timeout function in parameter 6-01 Live Zero Timeout Function.
6-13 Terminal 53 High Current
Default value:
20 mA
Setup:
All setups
Data type:
Int16
Enter the high current value corresponding to the high reference/feedback set in parameter 6-15 Terminal 53 High Ref./Feedb. Value.
280
| © 2024.09
5 V
10 V
Par 6-xx
Analog input
'High Voltage'or
'High Current'
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, -10.00 - par. 6-11 V
-2
True
Range, par. 6-10 V - 10 V
-2
True
Range, 0 - par. 6-13 mA
-5
True
Range, par. 6-12 mA - 20 mA
-5
True
AU275636650261en-003201 / 130R0334