Programming Guide | VLT® AutomationDrive FC 301/FC 302
12-11 Link Duration
Default value:
Size related
Setup:
All setups
Data type:
TimeDifferenceWithDateIndication
Shows the duration of the present link on each port in dd:hh:mm:ss.
12-12 Auto Negotiation
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Configures auto negotiation of Ethernet link parameters, for each port: ON or OFF. Link Speed and Link Duplex can be configured in
parameter 12-13 Link Speed and parameter 12-14 Link Duplex.
Option
Name
[0]
Off
[1]
On
12-13 Link Speed
Default value:
Setup:
2 setups
Data type:
Uint8
Forces the link speed for each port in 10 Mbps or 100 Mbps. If parameter 12-12 Auto Negotiation is set to [0] On, this parameter is read-
only and shows the actual link speed. If no link is present, None is shown.
Option
Name
[0]
None
[1]
10 Mbps
[2]
100 Mbps
12-14 Link Duplex
Default value:
Setup:
2 setups
Data type:
Uint8
In POWERLINK, this parameter is locked to half duplex.
396
| © 2024.09
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
  NOTICE
Parameter Descriptions
Range, 0 - 0, Array [2]
0
True
Option
True
Option, Array [2]
True
Option, Array [2]
True
AU275636650261en-003201 / 130R0334