Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[0]*
Master related
[1]
Follower related
17-97 Number of CAM Cycles
Default value:
0
Setup:
All setups
Data type:
Uint16
This parameter is only available in software version 48.96 and newer.
Set the number of CAM cycles which is executed by the Activate CAM cycles signal on a digital input or fieldbus control word bit.
17-98 CAM Cycles Start Delay
Default value:
0 AbsolutePositionUnit
Setup:
All setups
Data type:
Int32
This parameter is only available in software version 48.96 and newer.
Set a delay in absolute position units for the Activate CAM cycles signal.
Parameter Group 18-** Data Readouts 2
6.19
18-0* Maintenance Log
6.19.1
The following parameters are only available in FC 302:
Parameter 18-00 Maintenance Log: Item
l
Parameter 18-01 Maintenance Log: Action
l
Parameter 18-02 Maintenance Log: Time
l
Parameter 18-03 Maintenance Log: Date and Time
l
This parameter group contains the last 10 preventive maintenance events. Maintenance log 0 is the latest and maintenance log 9 is the
oldest. By selecting 1 of the logs and pressing [OK], the maintenance item, action, and time of the occurrence are shown in parameter
18-00 Maintenance Log: Item – parameter 18-03 Maintenance Log: Date and Time.
The alarm log key allows access to both alarm log and maintenance log.
600
| © 2024.09
Description
Offset execution is distributed over the offset execution distance
traveled by the master.
Offset execution is distributed over the offset execution distance
traveled by the follower.
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter type:
Conversion index:
Change during operation:
NOTICE
NOTICE
Parameter Descriptions
Range, 0 - 65535
0
True
Range, 0 - 2147483647
AbsolutePositionUnit
0
True
AU275636650261en-003201 / 130R0334