Programming Guide | VLT® AutomationDrive FC 301/FC 302
12-63 Basic Ethernet Timeout
5000.000 ms
Setup:
All setups
Data type:
Uint32
This parameter is the basic Ethernet timeout in ms. This parameter is mapped to Object 1F99h. If the POWERLINK interface does not
receive a SoC frame within the specified time, the interface shifts to standard Ethernet mode. This feature is available from version 2.00 of
the POWERLINK interface.
12-66 Threshold
Default value:
15
Setup:
All setups
Data type:
Uint32
This parameter holds 6 threshold values. If 1 of these thresholds are exceeded, the POWERLINK interface exits operational mode. The
parameters are set to optimal settings and should not be changed. The actual value of the counters can be read out via parameter 12-67
Threshold Counters.
12-67 Threshold Counters
Default value:
0
Setup:
All setups
Data type:
Uint32
This parameter holds 6 counters. The counter reflects the actual value in the POWERLINK interface. Counters increase with a count of 8 at
detection of an error and decrease with a count of 1 when no errors are detected. The values are read-only.
12-68 Cumulative Counters
Default value:
0
Setup:
All setups
Data type:
Uint32
Loss of SoC Cumulative. This parameter reflects the value in object 1C0Bh, sub-index 1.
12-69 Ethernet POWERLINK Status
Default value:
0
Setup:
All setups
Data type:
Uint32
This parameter shows various status and error conditions for the Ethernet POWERLINK connection.
© 2024.09
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275636650261en-003201 / 130R0334 |
Parameter Descriptions
Range, 0 - 2000000.000 ms
-3
True
Range, 0 - 2000000000, Array
[6]
0
True
Range, 0 - 4294967295, Array
[6]
0
True
Range, 0 - 2147483647, Array
[6]
0
True
Range, 0 - 4294967295
0
True
411