Programming Guide | VLT® AutomationDrive FC 301/FC 302
U
m
Par.1-60
100%
60%
0%
Changeover
Figure 39: Changeover
1-61 High Speed Load Compensation
Default value:
100%
Setup:
All setups
Data type:
Int16
Parameter 1-61 High Speed Load Compensation only has effect when parameter 1-10 Motor Construction = [0] Asynchron.
Enter the % value to compensate voltage in relation to load when the motor is running at high speed and obtain the optimum U/f
characteristic. The motor size determines the frequency range within which this parameter is active.
Motor size
0.25–7.5 kW
11–45 kW
55–maximum powerHz size kW
1-62 Slip Compensation
Default value:
Size related
Setup:
All setups
Data type:
Int16
Enter the % value for slip compensation to compensate for tolerances in the value of n
that is on the basis of the nominal motor speed n
Speed closed loop or [2] Torque torque control with speed feedback or when parameter 1-01 Motor Control Principle is set to [0] U/f.
112
| © 2024.09
Par.1-61
f
out
Parameter type:
Conversion index:
Change during operation:
NOTICE
Changeover
>10 Hz
>5 Hz
>3–4
Parameter type:
Conversion index:
Change during operation:
. This function is not active when parameter 1-00 Configuration Mode is set to [1]
M,N
Parameter Descriptions
Range, 0 - 300%
0
True
Range, -500 - 500%
0
True
. Slip compensation is calculated automatically,
M,N
AU275636650261en-003201 / 130R0334