Programming Guide | VLT® AutomationDrive FC 301/FC 302
Setup:
All setups
Data type:
Int32
This parameter is only available with software version 48.XX.
Set the master home position in position units which are used by master homing function.
17-9* Position Configuration
6.18.9
17-90 Absolute Position Mode
Default value:
[0] Standard
Setup:
All setups
Data type:
Uint8
This parameter is only available with software version 48.XX.
Select the behavior when executing consecutive absolute positioning commands.
Option
Name
[0]*
Standard
[1]
Buffered
17-91 Relative Position Mode
Default value:
[0] Target position
Setup:
All setups
Data type:
Uint8
This parameter is only available with software version 48.XX.
Select which reference to use for relative positioning commands.
596
| © 2024.09
Conversion index:
Change during operation:
NOTICE
Parameter type:
Conversion index:
Change during operation:
NOTICE
Description
When the drive receives a new absolute positioning command
while the previous command is still in progress, it executes the
new positioning command immediately without completing the
previous positioning.
When the drive receives a new absolute positioning command
while the previous positioning command is still in progress, it
completes the previous command and then executes the new
positioning command. Only 1 positioning command can be
buffered at a time.
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter Descriptions
0
True
Option
–
False
Option
–
False
AU275636650261en-003201 / 130R0334