Programming Guide | VLT® AutomationDrive FC 301/FC 302
A manual initialization also resets serial communication, RFI filter settings, and fault log settings.
Procedure
1.
Remove power to the unit and wait for the display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until an
audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
Parameter 15-00 Operating Hours
¢
Parameter 15-03 Power Up's
¢
Parameter 15-04 Over Temp's
¢
Parameter 15-05 Over Volt's
¢
Start-up takes slightly longer than normal.
46
| © 2024.09
NOTICE
How to Program
AU275636650261en-003201 / 130R0334
Need help?
Do you have a question about the VLT AutomationDrive FC 301 and is the answer not in the manual?
Questions and answers