Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[2]
Local
[3]
Linked to H/A MCO
3-14 Preset Relative Reference
Default value:
0%
Setup:
All setups
Data type:
Int32
The actual reference, X, is increased or decreased with percentage Y, which gives the resulting actual reference, Z. The actual reference (X)
is the sum of the inputs selected in:
Parameter 3-15 Reference Resource 1.
l
Parameter 3-16 Reference Resource 2.
l
Parameter 3-17 Reference Resource 3.
l
Parameter 8-02 Control Word Source.
l
Y
Resulting
Relative
Z
actual
X
Z=X+X*Y/100
reference
Figure 52: Preset Relative Reference
-100
0
Figure 53: Actual Reference
3-15 Reference Resource 1
Default value:
–
© 2024.09
Z
X
Y
100
%
P 3-14
Description
Use local reference in both hand-on and auto-on mode.
NOTICE
When set to [2] Local, the drive starts with this setting
again after a power-down.
Select this option to enable the FFACC factor in parameter 32-66
Acceleration Feed-Forward. Enabling FFACC reduces jitter and
makes the transmission from the motion controller to the control
card of the drive faster. This leads to faster response times for
dynamic applications and position control. For more information
about FFACC, see VLT® Motion Control MCO 305 Operating
Instructions.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
AU275636650261en-003201 / 130R0334 |
Parameter Descriptions
Range, -200 - 200%
-2
True
Option
151