Programming Guide | VLT® AutomationDrive FC 301/FC 302
Use this parameter to select the type of SS1 safety function.
Option
Name
[0]*
Delay
[1]
Ramp (slope)
[2]
Ramp (time)
42-41 Ramp Profile
Default value:
[0] Linear
Setup:
All setups
Data type:
Uint8
Option
Name
[0]*
Linear
[2]
S-ramp const time
42-42 Delay Time
Default value:
1 s
Setup:
All setups
Data type:
Uint16
Configure the time during which STO must be activated.
42-43 Delta T
Default value:
2%
Setup:
All setups
Data type:
Uint8
T subtracts from the time in parameter 42-42 Delay Time to get the motor to stop before the timer expires.
42-44 Deceleration Rate
Default value:
1500/s
Setup:
All setups
Data type:
Uint16
Deceleration rate for the SS1 slope-based ramp type.
42-45 Delta V
Default value:
120 RPM
Setup:
All setups
746
| © 2024.09
Description
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Parameter Descriptions
Option
–
False
Range, 0.1 - 3600 s
0
False
Range, 0 - 99%
0
False
Range, 1 - 30000/s
0
False
Range, 1 - 10000 RPM
67
AU275636650261en-003201 / 130R0334