Programming Guide | VLT® AutomationDrive FC 301/FC 302
Shows the heat sink temperature at the location of the phase W IGBT power module. This measurement is not available in all enclosure
sizes. Parameter 16-34 Heatsink Temp. uses the value in this parameter.
43-13 PC Fan A Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Uint16
Shows the measured speed of fan A on the power card. Each power card has up to 3 fan connections. Place the fan in the drive according
to the Operating Guide. A typical placement for fan A is in the backchannel (the external fan). The value of this parameter is:
The actual fan speed when there is a DC fan in the drive.
l
Relative speed when there is an AC fan in the drive.
l
43-14 PC Fan B Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Uint16
Shows the measured speed of fan B on the power card. Each power card has up to 3 fan connections. Place the fan in the drive according
to the Operating Guide. A typical placement for fan B is on the enclosure door (the internal fan). The value of this parameter is:
The actual fan speed when there is a DC fan in the drive.
l
Relative speed when there is an AC fan in the drive.
l
43-15 PC Fan C Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Uint16
Shows the measured speed of fan C on the power card. Each power card has up to 3 fan connections. Place the fan in the drive according
to the Operating Guide. A typical placement for fan C is inside the enclosure (the mixing fan). The value of this parameter is:
The actual fan speed when there is a DC fan in the drive.
l
Relative speed when there is an AC fan in the drive.
l
43-2* Fan Pow.Card Status
6.38.4
This parameter group is only available in FC 302.
43-20 FPC Fan A Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Uint16
754
| © 2024.09
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Changing during operation:
  NOTICE
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - 65535, Array [8]
67
True
Range, 0 - 65535, Array [8]
67
True
Range, 0 - 65535, Array [8]
67
True
Range, 0 - 65535, Array [4]
67
True
AU275636650261en-003201 / 130R0334