Programming Guide | VLT® AutomationDrive FC 301/FC 302
Option
Name
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
8-33 Parity/Stop Bits
Default value:
[0] Even parity, 1 stop bit
Setup:
1 setup
Data type:
Uint8
Option
Name
[0]*
Even parity, 1 stop bit
[1]
Odd parity, 1 stop bit
[2]
No parity, 1 stop bit
[3]
No parity, 2 stop bits
8-34 Estimated Cycle Time
Default value:
0 ms
Setup:
2 setups
Data type:
Uint32
In noisy environments, the interface may be blocked due to overload or bad frames. This parameter specifies the time between 2
consecutive frames on the network. If the interface does not detect valid frames in that time, it flushes the receive buffer.
8-35 Minimum Response Delay
Default value:
10 ms
Setup:
1 setup
Data type:
Unt16
Specify the minimum delay time between receiving a request and transmitting a response. This is used for overcoming modem
turnaround delays.
8-36 Max Response Delay
Default value:
Size related
Setup:
1 setup
Data type:
Uint16
© 2024.09
Description
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU275636650261en-003201 / 130R0334 |
Parameter Descriptions
Option
–
True
Range, 0 - 1000000 ms
-3
True
Range, 1 - 10000 ms
-3
True
Range, 11 - 10001 ms
-3
True
333