Programming Guide | VLT® AutomationDrive FC 301/FC 302
18-27 Safe Opt. Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Int32
Shows the speed that the drive estimates and sends to the VLT® Safety Option MCB 15X.
Parameter 18-28 Safe Opt. Meas. Speed
Default value:
0 RPM
Setup:
All setups
Data type:
Int32
Shows the speed measured by the VLT® Safety Option MCB 15X.
18-29 Safe Opt. Speed Error
Default value:
0 RPM
Setup:
All setups
Data type:
In t32
Shows the difference between the speed measured by the VLT® Safety Option MCB 15X and the speed estimated by the drive.
18-3* Analog Input
6.19.5
Parameters in this group show data related to analog inputs.
18-36 Analog Input X48/2 [mA]
Default value:
0
Setup:
All setups
Data type:
Int32
View the actual current measured at input X48/2.
18-37 Temp. Input X48/4
Default value:
0
Setup:
All setups
Data type:
Int16
View the actual temperature measured at input X48/4. The temperature unit is based on the selection in parameter 35-00 Term. X48/4
Temperature Unit.
18-38 Temp. Input X48/7
Default value:
0
Setup:
All setups
606
| © 2024.09
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Parameter Descriptions
Range, -30000 - 30000 RPM
67
True
Range, -30000 - 30000 RPM
67
True
Range, -30000 - 30000 RPM
67
True
Range, -20 - 20
-3
True
Range, -500 - 500
0
True
Range, -500 - 500
0
AU275636650261en-003201 / 130R0334