Programming Guide | VLT® AutomationDrive FC 301/FC 302
35-1* Temp. Input X48/4
6.34.2
35-14 Term. X48/4 Filter Time Constant
Default value:
0.001 s
Setup:
All setups
Data type:
Uint16
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal X48/4. A
high time constant value improves dampening but also increases the time delay through the filter.
35-15 Term. X48/4 Temp. Monitor
Default value:
[0] Disabled
Setup:
All setups
Data type:
Uint8
This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature limits
in parameter 35-16 Term. X48/4 Low Temp. Limit and parameter 35-17 Term. X48/4 High Temp. Limit.
Option
Name
[0]*
Disabled
[1]
Enabled
35-16 Term. X48/4 Low Temp. Limit
Default value:
Size related
Setup:
All setups
Data type:
Int16
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/4.
35-17 Term. X48/4 High Temp. Limit
Default value:
Size related
Setup:
All setups
Data type:
Int16
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/4.
6.34.3
35-2* Temp. Input X48/7
35-24 Term. X48/7 Filter Time Constant
Default value:
0.001 s
Setup:
All setups
702
| © 2024.09
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Parameter Descriptions
Range, 0.001 - 10 s
0
True
Option
–
True
Range, -50 - par. 35-17 Term.
X48/4 High Temp. Limit
0
True
Range, par. 35-16 Term. X48/4
Low Temp. Limit - 204
0
True
Range, 0.001 - 10 s
0
AU275636650261en-003201 / 130R0334